ClimateMaster OE Series Manuel d'installation Page 7

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 56
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 6
7
climatemaster.com
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y
THE SMART SOLUTION FOR ENERGY EFFICIENCY
G e n e s i s L a r g e ( G L ) S e r i e s
Genesis Large (GL) Series
R e v. : 1 3 A p r i l , 2 0 0 9 B
Rev.: 13 April, 2009B
GLV080-120 Dimensional Data
Back Return Front Supply (BF)
Air Out
BSP
NRP
Return
Air
CAP
B
W
F
D
E
1
[2.54cm]
1
[2.54cm]
N
K
3
2
1
U
V
P
5
4
Back Return Top Supply (BT)
Air Out
BSP
Return
Air
CAP
B
F
D
3
2
1
Air Out
Return
Air
CAP
Front Return Back Supply (FB)
BSP
Air Out
BSP
CSP
Return
Air
CAP
Front Return Top Supply (FT)
C
M
L
O
Q
R
S
0.75
[1.9cm]
T
E
C
A
A
0.75
[1.9cm]
Rev.: 07/30/08B
Water Inlet 1-1/2" IPT
Water Outlet 1-1/2" IPT
Condensate Drain 1" IPT
High Voltage Access 1-3/8" or 1-3/4" K.O.
[3.49 or 4.45cm]
Low Voltage Access 1/2" [12.7cm] Hole.
CAP - Control Access Panel
BSP - Blower Service Panel
2
1
3
4
5
Legend
3' [91cm]
Service Access
(All Units)
5
NOTES:
-All Dimensions in inches [cm]
-Units require 3' [91cm] clearance for water connections, CAP, CSP and BSP Service access.
-All side panels are removable Except those identified by NRP(Non-Removable Panel)
-Overall cabinet height dimension does not include duct flange when in the top discharge configuration
-Overall cabinet width dimensions does not include duct flange when in the front or back discharge configuration
4
CSP
CSP
-Overall cabinet width dimensions does not include filter rack. 1” filter rack standard. 2” filter rack optional
CSP
NRP
NRP
NRP
3' [91cm]
Service Access
3' [91cm]
Service Access
3' [91cm]
Service Access
Notes:
1. Service access provided on front and rear only. No service
access from unit ends provided.
2. While clear access to all removable panels is not required,
it may be. Access to some panels will always be required.
Installer should take care to comply with all building codes
and insure adequate clearance for future eld service.
Model
Overall Cabinet
Discharge Connections
Duct Flange
(± 0.10in, ±2.5mm)
Water Connections Electrical Knockouts / Holes
Return Air Connections
Using Return Air Opening
A
Width
B
Depth
C
Height
D
Supply
Width
E
Supply
Depth
FK
1
Water
Inlet
L
2
Water
Outlet
M
3
Con-
densate
NOPQRS
Return
Depth
T
Return
Height
UVW
080
in.
cm.
29.0
73.7
41.0
104.1
71.5
181.6
14.7
37.3
15.8
40.1
11.2
28.4
4.0
10.2
7.4
18.7
14.5
36.8
20.5
52.1
2.1
5.3
20.6
52.3
1.0
2.5
3.1
7.9
34.8
88.4
23.4
59.4
25.4
64.5
3.1
7.9
22.6
57.4
100-
120
in.
cm.
29.0
73.7
41.0
104.1
71.5
181.6
18.8
47.6
16.1
40.9
5.8
14.7
4.0
10.2
7.4
18.7
14.5
36.8
20.5
52.1
2.1
5.3
20.6
52.3
1.0
2.5
3.1
7.9
34.8
88.4
23.4
59.4
25.4
65.4
3.1
7.9
22.6
57.4