Functional Troubleshooting
Fault Htg Clg Possible Cause Solution
Main power problems
XXGreen Status LED Off
Check line voltage circuit breaker and disconnect.
Check for line voltage between L1 and L2 on the contactor.
Check for 24VAC between R and C on CXM/DXM'
Check primary/secondary voltage on transformer.
HP Fault
Code 2
High Pressure
X Reduced or no water ow in cooling
Check pump operation or valve operation/setting.
Check water ow adjust to proper ow rate.
X Water Temperature out of range in cooling Bring water temp within design parameters.
X Reduced or no air ow in heating
Check for dirty air lter and clean or replace.
Check fan motor operation and air ow restrictions.
Dirty Air Coil- construction dust etc.
Too high of external static. Check static vs blower table.
X Air temperature out of range in heating Bring return air temp within design parameters.
XXOvercharged with refrigerant Check superheat/subcooling vs typical operating condition table.
XXBad HP Switch Check switch continuity and operation. Replace.
LP/LOC Fault
Code 3
Low Pressure / Loss of Charge
XXInsuf cient charge Check for refrigerant leaks
X Compressor pump down at start-up Check charge and start-up water ow.
LT1 Fault
Code 4
Water coil low
temperature limit
X Reduced or no water ow in heating
Check pump operation or water valve operation/setting.
Plugged strainer or lter. Clean or replace..
Check water ow adjust to proper ow rate.
X Inadequate antifreeze level Check antifreeze density with hydrometer.
X
Improper temperature limit setting (30°F vs
10°F [-1°C vs -2°C])
Clip JW3 jumper for antifreeze (10°F [-12°C]) use.
X Water Temperature out of range Bring water temp within design parameters.
XXBad thermistor Check temp and impedance correlation per chart
LT2 Fault
Code 5
Air coil low
temperature limit
X Reduced or no air ow in cooling
Check for dirty air lter and clean or replace.
Check fan motor operation and air ow restrictions.
Too high of external static. Check static vs blower table.
X Air Temperature out of range Too much cold vent air? Bring entering air temp within design parameters.
X
Improper temperature limit setting (30°F vs
10°F [-1°C vs -12°C])
Normal airside applications will require 30°F [-1°C] only.
XXBad thermistor Check temp and impedance correlation per chart.
Condensate Fault
Code 6
XXBlocked drain Check for blockage and clean drain.
XXImproper trap Check trap dimensions and location ahead of vent.
X Poor drainage
Check for piping slope away from unit.
Check slope of unit toward outlet.
Poor venting. Check vent location.
X Moisture on sensor Check for moisture shorting to air coil.
XXPlugged air lter Replace air lter.
xXRestricted Return Air Flow Find and eliminate restriction. Increase return duct and/or grille size.
Over/Under
Voltage Code 7
(Auto resetting)
XXUnder Voltage
Check power supply and 24VAC voltage before and during operation.
Check power supply wire size.
Check compressor starting. Need hard start kit?
Check 24VAC and unit transformer tap for correct power supply voltage.
XXOver Voltage
Check power supply voltage and 24VAC before and during operation.
Check 24VAC and unit transformer tap for correct power supply voltage.
Unit Performance Sentinel
Code 8
X Heating mode LT2>125°F [52°C] Check for poor air ow or overcharged unit.
X
Cooling Mode LT1>125°F [52°C] OR LT2<
40ºF [4ºC])
Check for poor water ow, or air ow.
Swapped Thermistor
Code 9
XXLT1 and LT2 swapped Reverse position of thermistors
ECM Fault - Code 10
XX
Blower does not operate
Check blower line voltage
Check blower low voltage wiring
Blower operating with incorrect air ow
Wrong unit size selection
Wrong unit family selection
Wrong motor size
Incorrect blower selection
Low Air Coil Pressure Fault
(ClimaDry) Code 11
X
Reduced or no air ow in cooling or ClimaDry
Check for dirty air lter and clean or replace
Check fan motor operation and air ow restrictions
Too high of external static - check static vs blower table
Air temperature out of range Too much cold vent air - bring entering air temp within design parameters
Bad pressure switch Check switch continuity and operation - replace
Low Air Coil Temperature
Fault - (ClimaDry) Code 12
X
Reduced air ow in cooling, ClimaDry, or
constant fan
Check for dirty air lter and clean or replace
Check fan motor operation and air ow restrictions
Too high of external static - check static vs blower table
Air temperature out of range Too much cold vent air - bring entering air temp within design parameters
Bad thermistor Check temp and impedance correlation per chart
Table Continued on Next Page