ClimateMaster DD Series Spécifications Page 16

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 56
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 15
TT Series 60Hz - HFC-410A Submittal Data Eng/I-P
ClimateMaster works continually to improve its products. As a result, the design and specications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer
Service Department at 1-405-745-6000 for specic information on the current design and specications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties,
but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.
Revised: 17 July, 2013LC356 - 16
Page ______ of ______
Performance Data – TT H/V/D 064 (Part Load)
Interpolation is permissible; extrapolation is not.
All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating.
AHRI/ISO certied conditions are 80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating.
Table does not reect fan or pump power corrections for AHRI/ISO conditions.
All performance is based upon the lower voltage of dual voltage rated units.
Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated.
Operation below 40°F EWT is based upon a 15% methanol antifreeze solution.
Operation below 60°F EWT requires optional insulated water/refrigerant circuit.
See performance correction tables for operating conditions other than those listed above.
See Performance Data Selection Notes for operation in the shaded areas.
EWT
°F
GPM
WPD Cooling - EAT 80/67 °F Heating - EAT 70°F
PSI FT TC SC
Sens/Tot
Ratio
kW HR EER HC kW HE LAT COP
20 12.0 5.2 11.9 Operation not recommended 28.6 2.75 19.3 84.0 3.1
30
6.0 0.9 2.1 57.1 41.6 0.73 1.50 62.2 38.1 32.2 2.76 22.7 86.0 3.4
9.0 2.5 5.7 56.9 42.3 0.74 1.45 61.8 39.2 33.6 2.77 24.1 86.8 3.6
12.0 4.1 9.6 56.5 42.6 0.75 1.44 61.4 39.1 34.4 2.77 24.9 87.2 3.6
40
6.0 0.5 1.1 56.4 40.7 0.72 1.64 62.0 34.4 37.6 2.79 28.0 89.0 3.9
9.0 1.9 4.3 57.0 41.3 0.73 1.54 62.3 37.1 39.4 2.80 29.8 90.0 4.1
12.0 3.4 7.9 57.1 41.7 0.73 1.50 62.2 38.1 40.4 2.81 30.8 90.6 4.2
50
6.0 0.2 0.6 54.8 39.8 0.73 1.85 61.1 29.7 43.1 2.82 33.5 92.1 4.5
9.0 1.5 3.5 56.0 40.4 0.72 1.70 61.8 33.0 45.3 2.84 35.7 93.4 4.7
12.0 3.0 6.9 56.5 40.8 0.72 1.63 62.0 34.6 46.6 2.85 36.9 94.1 4.8
60
6.0 0.2 0.4 52.4 38.9 0.74 2.11 59.6 24.8 48.8 2.86 39.0 95.3 5.0
9.0 1.4 3.1 54.1 39.5 0.73 1.93 60.6 28.1 51.4 2.89 41.5 96.8 5.2
12.0 2.7 6.3 54.8 39.9 0.73 1.84 61.1 29.8 52.8 2.90 42.9 97.6 5.3
70
6.0 0.2 0.4 49.6 37.9 0.76 2.42 57.8 20.4 54.4 2.91 44.5 98.5 5.5
9.0 1.3 3.0 51.5 38.6 0.75 2.21 59.0 23.3 57.3 2.94 47.3 100.1 5.7
12.0 2.6 6.0 52.4 38.9 0.74 2.11 59.6 24.8 58.9 2.96 48.8 101.0 5.8
80
6.0 0.2 0.6 46.5 36.7 0.79 2.78 56.0 16.7 59.9 2.97 49.8 101.6 5.9
9.0 1.3 3.1 48.5 37.5 0.77 2.55 57.2 19.0 63.1 3.00 52.9 103.3 6.2
12.0 2.6 5.9 49.5 37.8 0.76 2.44 57.8 20.3 64.8 3.03 54.5 104.3 6.3
90
6.0 0.3 0.7 43.3 35.3 0.82 3.18 54.1 13.6 65.3 3.03 55.0 104.6 6.3
9.0 1.4 3.2 45.2 36.2 0.80 2.93 55.2 15.4 68.7 3.08 58.1 106.4 6.5
12.0 2.6 6.0 46.2 36.6 0.79 2.81 55.8 16.5 70.4 3.11 59.8 107.4 6.6
100
6.0 0.3 0.8 40.2 33.9 0.84 3.62 52.5 11.1
Operation not recommended
9.0 1.4 3.2 42.0 34.7 0.83 3.36 53.4 12.5
12.0 2.6 6.0 43.0 35.2 0.82 3.23 54.0 13.3
110
6.0 0.3 0.6 37.4 32.4 0.87 4.09 51.3 9.1
9.0 1.3 3.1 38.9 33.2 0.85 3.81 52.0 10.2
12.0 2.5 5.8 39.8 33.7 0.85 3.68 52.3 10.8
120
6.0 0.0 0.0 35.1 31.0 0.88 4.59 50.8 7.6
9.0 1.1
2.6 36.3 31.7 0.87 4.30 51.0 8.4
12.0 2.3 5.4 37.0 32.2 0.87 4.16 51.2 8.9
Performance capacities shown in thousands of Btuh1,650 CFM Nominal Airow Heating, 1,500 CFM Nominal Airow Cooling
Vue de la page 15
1 2 ... 11 12 13 14 15 16 17 18 19 20 21 ... 55 56

Commentaires sur ces manuels

Pas de commentaire