THE SMART SOLUTION FOR ENERGY EFFICIENCY
Tranquility
®
30 (TT) Series
Rev.: 07/18/13
Cooling Heating
Air Limits
Min. ambient air, DB 45ºF [7ºC] 39ºF [4ºC]
Rated ambient air, DB 80.6ºF [27ºC] 68ºF [20ºC]
Max. ambient air, DB 130ºF [54.4ºC] 85ºF [29ºC]
Min. entering air, DB/WB *50/45ºF [10/7ºC] 40ºF [4.5ºC]
Rated entering air, DB/WB 80.6/66.2ºF [27/19ºC] 68ºF [20ºC]
Max. entering air, DB/WB 110/83ºF [43/28ºC] 80ºF [27ºC]
Water Limits
Min. entering water 30ºF [-1ºC] 20ºF [-6.7ºC]
Normal entering water 50-110ºF [10-43ºC] 30-70ºF [-1 to 21ºC]
Max. entering water 120ºF [49ºC] 90ºF [32ºC]
Commissioning Limits
Normal Water Flow
1.5 to 3.0 gpm / ton
[1.6 to 3.2 l/m per kW]
Unit Starting and Operating Conditions
Commissioning Conditions
Consult Table 9b for the particular model. Starting conditions vary depending upon model and are based upon the
following notes:
Notes:
1. Conditions in Table 9b are not normal or continuous operating conditions. Minimum/maximum limits are start-up
conditions to bring the building space up to occupancy temperatures. Units are not designed to operate under
these conditions on a regular basis.
2. Voltage utilization range complies with AHRI Standard 110.
Table 9b: Building Commissioning Limits
*If with ClimaDry
®
65/55°